What to study for each CEPSS-HC domain
Classification of Emergency Power Supply Systems (EPSSs)
Covers the NFPA 110 Level, Type, and Class system for emergency power supply systems, including Level 1 life-safety criticality and the Type 10 requirement to restore power within 10 seconds. It also covers how NFPA 99 applies that classification to the hospital Type 1 essential electrical system and its life safety, critical, and equipment branches.
Key skills
Identifying EPSS Level, Type, and Class designations, applying the 10-second restoration requirement, and mapping loads to the life safety, critical, and equipment branches
Classification of Stored Energy Emergency Power Supply Systems (SEPSS)
Covers the NFPA 111 classification of stored energy emergency power supply systems by Level, Type, and Class, paralleling the NFPA 110 framework. It addresses Type U uninterruptible performance and how stored-energy duration (Class) is specified for health care applications.
Key skills
Classifying a SEPSS by Level, Type, and Class, distinguishing Type U no-break systems, and specifying stored-energy runtime for a given load
Emergency Power Supply (EPSS): Energy Sources, Converters, and Accessories
Covers the engine-driven EPSS itself: prime movers, generators, and the fuel, cooling, lubrication, exhaust, starting, and control accessory systems that keep it running. It emphasizes starting batteries and chargers, engine heaters, day tanks, governors, voltage regulators, and remote annunciation in hospital service.
Key skills
Evaluating prime mover and alternator components, maintaining starting and charging systems, managing fuel quality and supply, and interpreting EPSS alarms and accessories
Stored Energy Emergency Power Supply (SEPSS): Energy Sources, Converters, Inverters, and Accessories
Covers the stored-energy chain under NFPA 111: batteries as the energy source, chargers that restore them, and inverters that convert stored direct current to alternating-current output. It addresses battery capacity, aging, and double-conversion UPS operation for sensitive health care loads.
Key skills
Sizing and assessing battery capacity, explaining charger and inverter functions, and recognizing capacity loss that reduces SEPSS runtime
Transfer Switch Equipment and Protection
Covers automatic transfer switch operation, sensing, and control time delays, including the requirement that essential branches transfer within 10 seconds in a Type 10 system. It also addresses separate transfer switches for the life safety, critical, and equipment branches, bypass isolation, transition types, withstand and closing ratings, selective coordination, and ground-fault protection philosophy.
Key skills
Selecting and applying transfer switches per branch, setting start, retransfer, and cooldown delays, coordinating overcurrent protection, and verifying switch ratings against available fault current
Installation and Environmental Consideration
Covers siting and installing the EPSS so it can run continuously at full load for its full Class duration, including fire separation of the generator room, ventilation and combustion air, and exhaust routing. It also addresses fuel storage sizing and containment, flood, cold-weather and seismic considerations, working clearances, noise, and emergency lighting in the EPSS room.
Key skills
Reviewing generator room separation and ventilation, sizing and protecting fuel storage, and accounting for flood, temperature, vibration, and access in EPSS installations
Routine Maintenance and Operational Testing
Covers the NFPA 110 Chapter 8 maintenance and testing program as applied by NFPA 99 in health care facilities, including weekly inspections and monthly loaded exercise of at least 30 minutes at adequate load. It also covers load bank testing, the 36-month 4-hour extended test, transfer switch exercise, battery and fuel testing, failure correction and retest, and the records required for survey and AHJ review.
Key skills
Performing weekly inspections and monthly loaded tests, planning load bank and 36-month extended tests, testing batteries and fuel, and documenting inspections, tests, and corrective actions