CEPSS-HC Certified Emergency Power Systems Specialist for Health Care Facility Managers โ Exam Overview
Quick Facts
The Certified Emergency Power Systems Specialist for Health Care Facility Managers (CEPSS-HC) exam has 100 multiple-choice questions with a 3-hour time limit. It is an open-book exam based on NFPA 99 (2012) and the 2010 editions of NFPA 110 and NFPA 111, and it is available in English only. NFPA does not publish a passing score or a price for this exam in the program overview.
Who this exam is for
Health care facility managers, facility engineers, and plant operations staff responsible for emergency and standby power systems in hospitals and other health care occupancies. It also serves compliance staff who must demonstrate that essential electrical systems meet NFPA 99, NFPA 110, and NFPA 111 requirements under the CMS emergency-preparedness framework.
Exam Domains
Classification of Emergency Power Supply Systems (EPSSs) โ 11%
Covers the NFPA 110 Level, Type, and Class system for emergency power supply systems, including Level 1 life-safety criticality and the Type 10 requirement to restore power within 10 seconds. It also covers how NFPA 99 applies that classification to the hospital Type 1 essential electrical system and its life safety, critical, and equipment branches.
Classification of Stored Energy Emergency Power Supply Systems (SEPSS) โ 5%
Covers the NFPA 111 classification of stored energy emergency power supply systems by Level, Type, and Class, paralleling the NFPA 110 framework. It addresses Type U uninterruptible performance and how stored-energy duration (Class) is specified for health care applications.
Emergency Power Supply (EPSS): Energy Sources, Converters, and Accessories โ 15%
Covers the engine-driven EPSS itself: prime movers, generators, and the fuel, cooling, lubrication, exhaust, starting, and control accessory systems that keep it running. It emphasizes starting batteries and chargers, engine heaters, day tanks, governors, voltage regulators, and remote annunciation in hospital service.
Stored Energy Emergency Power Supply (SEPSS): Energy Sources, Converters, Inverters, and Accessories โ 5%
Covers the stored-energy chain under NFPA 111: batteries as the energy source, chargers that restore them, and inverters that convert stored direct current to alternating-current output. It addresses battery capacity, aging, and double-conversion UPS operation for sensitive health care loads.
Transfer Switch Equipment and Protection โ 25%
Covers automatic transfer switch operation, sensing, and control time delays, including the requirement that essential branches transfer within 10 seconds in a Type 10 system. It also addresses separate transfer switches for the life safety, critical, and equipment branches, bypass isolation, transition types, withstand and closing ratings, selective coordination, and ground-fault protection philosophy.
Installation and Environmental Consideration โ 14%
Covers siting and installing the EPSS so it can run continuously at full load for its full Class duration, including fire separation of the generator room, ventilation and combustion air, and exhaust routing. It also addresses fuel storage sizing and containment, flood, cold-weather and seismic considerations, working clearances, noise, and emergency lighting in the EPSS room.
Routine Maintenance and Operational Testing โ 25%
Covers the NFPA 110 Chapter 8 maintenance and testing program as applied by NFPA 99 in health care facilities, including weekly inspections and monthly loaded exercise of at least 30 minutes at adequate load. It also covers load bank testing, the 36-month 4-hour extended test, transfer switch exercise, battery and fuel testing, failure correction and retest, and the records required for survey and AHJ review.
Preparing for CEPSS-HC
Work through the practice questions in study mode first, read every explanation, then switch to timed practice. Weight your revision by the domain weightings above and revisit the topics you score lowest on until your practice scores are consistent.
Write Your Review on CEPSS-HC Certified Emergency Power Systems Specialist for Health Care Facility Managers
CEPSS-HC Customer Reviews
No reviews yet
Be the first to share your experience with this exam.