Classification of Emergency Power Supply Systems (EPSSs)
Covers how NFPA 110 classifies an EPSS by Type, Class, and Level, including the maximum permitted interruption time, the minimum operating duration at rated load, and the consequence-of-failure basis for Level 1 and Level 2 systems. It also covers applying a complete classification, such as Type 10, Class 48, Level 1, to a real facility load.
Key skills
Interpreting Type, Class, and Level designations, selecting a classification for a given load, and explaining what each element requires of the installation.
Classification of Stored Energy Emergency Power Supply Systems (SEPSS)
Covers how NFPA 111 classifies a stored energy emergency power supply system by Type, Class, and Level, including uninterruptible Type U performance and endurance based on stored energy rather than stored fuel. It also covers distinguishing SEPSS classification from the generator-based EPSS classification in NFPA 110.
Key skills
Interpreting SEPSS Type, Class, and Level designations and identifying which systems are classified under NFPA 111.
Emergency Power Supply (EPSS) Energy Sources, Converters and Accessories
Covers the energy sources, converters, and accessories of an engine-driven EPSS, including diesel and gaseous prime movers, the alternator as converter, starting batteries and chargers, governors, voltage regulation, and coolant heating. It also covers fuel supply choices and the reliability trade-offs between on-site stored fuel and utility-supplied gas.
Key skills
Identifying EPS components and accessories, explaining starting and control functions, and evaluating fuel source reliability for Level 1 service.
Stored Energy Emergency Power Supply (SEPSS): Energy Sources, Converters, Inverters, and Accessories
Covers the energy sources, converters, inverters, and accessories of a SEPSS, including flooded and valve-regulated lead-acid batteries, rectifiers and chargers, double-conversion UPS operation, static bypass, and flywheel storage. It also covers battery capacity sizing in ampere-hours against the required class duration.
Key skills
Explaining inverter and rectifier functions, comparing battery technologies, and sizing stored energy for a required runtime.
Transfer Switch Equipment and Protection
Covers automatic transfer switch operation and protection, the largest part of the blueprint, including open, closed, and delayed transition, time delays for starting, transfer, retransfer, and cooldown, and in-phase monitoring. It also covers bypass-isolation switches, withstand and closing ratings, selective coordination of overcurrent devices, and ground-fault alarm philosophy for emergency systems.
Key skills
Explaining ATS sequences and timing, selecting transition types for motor loads, and verifying transfer equipment ratings and protective coordination.
Installation and Environmental Consideration
Covers installation and environmental considerations for EPSS and SEPSS equipment, including dedicated fire-separated generator rooms, ventilation and exhaust, fuel storage sizing, wiring separation, and remote annunciation. It also covers siting decisions involving flooding, seismic exposure, weather, security, and access for maintenance.
Key skills
Applying NFPA 110 and NFPA 111 installation requirements, evaluating equipment locations, and identifying environmental risks to system reliability.
Routine Maintenance and Operational Testing
Covers routine maintenance and operational testing under NFPA 110 Chapter 8 and NFPA 111, including weekly inspections, monthly exercise of at least 30 minutes at adequate load, and monthly transfer switch operation. It also covers annual fuel quality testing, the annual load bank profile for underloaded diesel sets, the 36-month extended test for Level 1 systems, record keeping, and correction of deficiencies.
Key skills
Planning inspection and exercise schedules, evaluating loaded test results, and documenting and closing out maintenance deficiencies.