CEPSS Certified Emergency Power Systems Specialist for Facility Managers โ Exam Overview
Quick Facts
The Certified Emergency Power Systems Specialist for Facility Managers (CEPSS) exam contains 100 multiple-choice questions with a 3-hour time limit. It is an open-book exam based on the 2016 editions of NFPA 110 and NFPA 111 and is available in English only. NFPA lists the initial application/exam fee at $499, and NFPA does not publish a passing score for this exam.
Who this exam is for
Facility managers and building operations professionals responsible for emergency power supply systems (EPSS) and stored energy emergency power supply systems (SEPSS) in their facilities. It suits those who specify, oversee, or maintain generators, batteries, UPS systems, and transfer equipment to NFPA 110 and NFPA 111.
Exam Domains
Classification of Emergency Power Supply Systems (EPSSs) โ 9%
Covers how NFPA 110 classifies an EPSS by Type, Class, and Level, including the maximum permitted interruption time, the minimum operating duration at rated load, and the consequence-of-failure basis for Level 1 and Level 2 systems. It also covers applying a complete classification, such as Type 10, Class 48, Level 1, to a real facility load.
Classification of Stored Energy Emergency Power Supply Systems (SEPSS) โ 7%
Covers how NFPA 111 classifies a stored energy emergency power supply system by Type, Class, and Level, including uninterruptible Type U performance and endurance based on stored energy rather than stored fuel. It also covers distinguishing SEPSS classification from the generator-based EPSS classification in NFPA 110.
Emergency Power Supply (EPSS) Energy Sources, Converters and Accessories โ 11%
Covers the energy sources, converters, and accessories of an engine-driven EPSS, including diesel and gaseous prime movers, the alternator as converter, starting batteries and chargers, governors, voltage regulation, and coolant heating. It also covers fuel supply choices and the reliability trade-offs between on-site stored fuel and utility-supplied gas.
Stored Energy Emergency Power Supply (SEPSS): Energy Sources, Converters, Inverters, and Accessories โ 11%
Covers the energy sources, converters, inverters, and accessories of a SEPSS, including flooded and valve-regulated lead-acid batteries, rectifiers and chargers, double-conversion UPS operation, static bypass, and flywheel storage. It also covers battery capacity sizing in ampere-hours against the required class duration.
Transfer Switch Equipment and Protection โ 25%
Covers automatic transfer switch operation and protection, the largest part of the blueprint, including open, closed, and delayed transition, time delays for starting, transfer, retransfer, and cooldown, and in-phase monitoring. It also covers bypass-isolation switches, withstand and closing ratings, selective coordination of overcurrent devices, and ground-fault alarm philosophy for emergency systems.
Installation and Environmental Consideration โ 16%
Covers installation and environmental considerations for EPSS and SEPSS equipment, including dedicated fire-separated generator rooms, ventilation and exhaust, fuel storage sizing, wiring separation, and remote annunciation. It also covers siting decisions involving flooding, seismic exposure, weather, security, and access for maintenance.
Routine Maintenance and Operational Testing โ 21%
Covers routine maintenance and operational testing under NFPA 110 Chapter 8 and NFPA 111, including weekly inspections, monthly exercise of at least 30 minutes at adequate load, and monthly transfer switch operation. It also covers annual fuel quality testing, the annual load bank profile for underloaded diesel sets, the 36-month extended test for Level 1 systems, record keeping, and correction of deficiencies.